Category: PCB Universal Screw Terminal Block
Item | Data | ||||
APPROVAL | |||||
Test standard | IEC61984/ UL1059 | ||||
Pitch [mm] | 5 | ||||
Poles | 02-12P | ||||
IEC61984 Test data | / | ||||
Rated voltage [V] | 250 | ||||
Rated current [A] | 12 | ||||
Rated connection capacity(solid/stranded) [mm²] | 0.2-2.5 | ||||
Surge voltage category/pollution degree/material group | III/2/I | ||||
Rated impulse voltage [KV] | 4 | ||||
Rated torque [N.m] | 0.5 | ||||
UL1059Test data | UL File Number E228872 | ||||
Use group | B | C | D | ||
Rated voltage [V] | 300 | / | 300 | ||
Rated current [A] | 16 | / | 10 | ||
Rated connection capacity (solid/stranded) [AWG] | 28~12 | ||||
Rated torque [Lb. in] | 4.43 | ||||
General data | / | ||||
Screw | M3 | ||||
Inflammability class UL94 | V-0 | ||||
Ambient temperature [℃] | -40~+105 | ||||
Relative humidity | 5%-95% | ||||
Inspection standard | MIL-STD-105E II | ||||
AQL | 0.65 | ||||
Warranty | 12 months | ||||
Material and plating | / | ||||
Housing | PA66 | ||||
Screws | Steel,Zn-Ni plated | ||||
Contact | Copper alloy,Sn Plated | ||||
Cage | Copper alloy,Ni Plated | ||||
Wire connecting | |||||
Recommended stripping length 5-6mm; | |||||
1.)For solid wire, stripping wire to the appointed length, then tightening with rated torque. | |||||
2.)For stranded wire: stripping wire to the appointed length, mating with corresponding type of ferrule, then tightening with rated torque. | |||||
Notes: Tightening process should be steady, can’t use explosive force. |